Transcona Ice Dam Correction
All projects
VentilationDiagnosticsThermal scan

Transcona Ice Dam Correction

Two winters of interior staining that three previous contractors treated as a shingle problem. It was never a shingle problem.

Location
Transcona, Winnipeg
System
Ventilation rebuild + eave protection
Scope
28 squares
On site
2 days
Completed
2024

The challenge

Bathroom fans terminating in the attic, blocked soffit intake, and R-24 insulation compressed under a walkway of stored boxes.

What we specified

Ducted both fans through the roof, installed 34 continuous intake baffles, blew attic insulation to R-60, and carried membrane 1.2 m up the slope.

The outcome

Zero dam formation the following winter, verified by a February thermal scan at no charge.